Grid equipment is the least forgiving market for embedded electronics: wide temperature, continuous vibration, a twenty-year service expectation, redundant networks, surge on every port, and a security posture that can be audited. A single-board computer is not a protection relay, and it should never be sold as one. What it can be is the monitoring, gateway and HMI layer around the relay, the meter and the breaker controller.
What the equipment requires
- Redundant networking. Two independent Ethernet ports for station-bus and process-bus, or for PRP/HSR redundancy handled by an external switch.
- Serial fieldbus. IEC 60870-5-101/104, Modbus RTU and DL/T 645 all land on RS-485 or RS-232 ports; isolation is mandatory.
- Wide temperature. A cabinet in a tropical substation or a northern yard is -40 to +75 C inside the enclosure at times.
- Longevity. Ten to twenty years of supply and a frozen BOM; the module datasheet has to carry an industrial temperature grade.
- Security. Signed images, secure boot, a disabled debug port and an auditable update path.
Recommended configuration
| Function | Recommended TOPEET part |
|---|---|
| Bay controller HMI, local SCADA client, data concentrator | iTOP-RK3568 Single Board Computer, industrial -40 to +85 C SKU, dual Gigabit Ethernet, CAN, RS-485, LVDS panel output |
| RTU / DTU with dual network ports and CAN FD | iTOP-RK3506 Single Board Computer: two 100 Mbit industrial RJ45, 2x CAN FD up to 8 Mbps, 6 UART, -20 to +80 C |
| Serial aggregation for legacy protection and meters | 16-port RS-485 / RS-232 to Ethernet Serial Server |
| Wireless backhaul for remote feeders | iTOP-RK3568 Single Board Computer with 5G Module |
| Panel in the cabinet door | 10.1-inch Display, 1024x600, Metal Frame |
| CAN / RS-485 interface board | CAN / RS-485 Module |
Interface checklist
- Two Ethernet ports on separate MACs so a station-bus fault cannot take the HMI down.
- Isolated RS-485 with 3 kV isolation and surge protection on the terminal block.
- CAN FD for the newer breaker and inverter controllers.
- RTC with a backup cell: event logs are useless without a correct timestamp after a power cut.
- Watchdog that resets the host but not the fieldbus transceivers.
- Conformal coating and a metal enclosure with a proper earth stud.
What we would validate with you
IEC 61000-4-x immunity at the enclosure level, protocol conformance against your RTU test bench, temperature cycling from cold start to full load, and the update path that a utility security review will ask about. We will also tell you plainly which parts of the design must not be carried by a Linux host.
Documents
Industrial-grade datasheets, schematics and BSP sources are in the resource portal. 12-month warranty, engineering support by email.
Frequently asked questions
Can a single board computer replace a protection relay?
No, and it should never be sold as one. It belongs in the monitoring, gateway and HMI layer around the relay, the meter and the breaker controller.
Which interfaces matter, and on which board?
The iTOP-RK3568 industrial SKU (-40 to +85 C) provides dual Gigabit Ethernet, CAN, RS-485 and LVDS panel output for a bay controller HMI or data concentrator. The iTOP-RK3506 suits an RTU or DTU with two 100 Mbit industrial RJ45 ports, two CAN FD channels to 8 Mbps, six UARTs and a -20 to +80 C rating.
What does a utility security review actually ask for?
IEC 61000-4-x immunity measured at the enclosure level, protocol conformance against your own RTU test bench, temperature cycling from cold start to full load, and a documented update path.